TTSGTomoe Transtech Specialty Gases Pte Ltd JapaneseSite Map
Products Quickmenu:

" Valve Shutter" is a safety system developed to prevent secondary accidents due to earthquakes, and to forestall gas explosions and gas poisoning due to gas leaks, using an emergency shutoff valve on the gas cylinder.

Valve Shutter (VS-100 Mark II)r
The valve shutter is a safety system developed to prevent secondary accidents due to earthquakes, and to forestall gas explosions and gas poisoning due to gas leaks, using an emergency shutoff valve on the gas cylinder. Having thoroughly considered explosion prevention, the operating signals use air pressure so that compressed air, nitrogen gas, etc. (0.29 Mpa) can be used within the plant, and a power spring is used in the shutoff valve mechanism. One-touch mounting on existing gas cylinders is possible.
Operating Method: Valve open (manual)
Valve close (operated using power spring)
Installation: -Supply the gas pressure. (3kgf/ cm2)
-Set the valve indicatorpoint to "Open Position" manually
-Automatically valve shut off by the board spring
-Supply gas fitting...6/4mm flexible tubing
Operation Check: Equipped with a Color Indicator
Suitable Air Pressure: 0.29 (Mpa)
Operating Pressure Range: 0.19 to 0.68 (Mpa)
Connection: 6 x 4-mm quick connectors
Control Box (VSC-101)
Alarm Input Signal: 5 points
Input Signal: Dry Signal or DC Signal (10-30V), slection
Control: Manual or Automatic
Noise: DC 1000V, No effect
Dimension: 220mm (width) * 136mm (Breadth) * 130mm (Height)